Fire extinguisher servicing in Ireland: what the official guidance says
Extinkto guide · official sources re-read on 25 November 2026
Do you service fire extinguishers for clients in Ireland, or run a fire safety service company? Here is what the official Irish guidance says: who is responsible, how often, what happens at a service and what must be kept on record. Each point refers to an official document, listed at the bottom of the page.
This page is general information, not legal advice. For a specific building, the official texts, the standards and the fire authority's requirements prevail.
Who is responsible
- Under Section 18(2) of the Fire Services Acts 1981 and 2003, every person having control over premises to which the section applies must take all reasonable measures to guard against the outbreak of fire, provide reasonable fire safety measures, and ensure they are applied at all times.
- The duty is on the person having control of the premises — your client. You carry out the servicing they entrust to you.
How often
- Annual service: fire-fighting equipment "must be serviced annually by a competent person (usually a fire safety engineer)" (HSA information sheet, 2023).
- The Department of Housing's Fire Safety Guide (March 2022, Table 2) states that all portable fire extinguishers shall be maintained in accordance with Clause 9 of I.S. 291 at intervals not exceeding 12 ± 1 month.
- Discharge test: "Each extinguisher should be test discharged and refilled every 3 years" (HSA).
- After use: any extinguisher used in a fire, for training or otherwise discharged should be recharged immediately (Fire Safety Guide, Table 2).
- Hose reels: maintained annually in accordance with I.S. EN 671-3, and every 5 years all hoses pressurised to maximum working pressure (Fire Safety Guide, Table 2).
What happens at a service
According to the HSA, the fire safety engineer visually inspects all fire-fighting equipment, weighs each extinguisher, tests the gauge and replaces the seal where the hose joins the cylinder. Each extinguisher is marked with its next due date, and the engineer should give a certificate of service once the work is complete.
What the occupier checks in between
- Daily: all the points where extinguishers or hose reels are located; missing ones replaced immediately.
- Weekly: gauges working, controls set and accessible, equipment clean, undamaged and in place.
- Monthly: the people who may have to use the equipment are trained, new employees included.
Source: Fire Safety Guide, Table 2.
What to keep on record: the Fire Safety Register
- A Fire Safety Register should be maintained for all premises where Section 18(1) applies. It should be kept on the premises at all times, kept up to date and be available for inspection by an authorised officer of the fire authority (Fire Safety Guide, section 5.7).
- It is a "living" document, with daily, weekly, monthly, quarterly and annual records of fire safety checks.
- The HSA advises keeping a record of all equipment inspections and servicing, staff training and fire drills: "A fire register is useful for this purpose."
The register belongs to your client. Your dated, signed service reports, with the engineer and the equipment listed, are what allow them to keep it.
Other systems
Fire alarms (I.S. 3218), emergency lighting (I.S. 3217), fire doors and other systems have their own checks and intervals, set out in Table 2 of the Fire Safety Guide. The standards themselves (I.S. 291, I.S. 3218, I.S. 3217) are sold by the NSAI.
What this guide does not cover
- The full text of I.S. 291, which is a paid standard.
- Requirements specific to a building set by the fire authority or by insurers.
- Northern Ireland, where different rules apply.
How Extinkto helps
Extinkto is a tracking tool for service companies. It does not replace your competence or your client's Fire Safety Register: the engineer remains responsible for their findings and the certificates they issue. It helps you make sure nothing is missed:
- Each client's equipment: every extinguisher has its record, its location, its history and its QR label.
- Due dates: the next service is worked out for each piece of equipment from the intervals you set (the 3-yearly discharge test too, in "My settings"), with reminders at 30, 15 and 7 days.
- The service report signed by the client on your phone: a numbered PDF with the equipment, the engineer, the next due date and the signature, sent to the client in one tap.
- The client portal: your client sees their equipment, upcoming services and signed service reports.
Try Extinkto for 30 days, no card needed
Sources
Official documents re-read on 25 November 2026:
- Health and Safety Authority (HSA), "Fire Extinguisher – Safety Checks" information sheet, 2023 (PDF).
- Department of Housing, Local Government and Heritage, "Fire Safety Guide for Building Owners and Operators – Guide for persons having control under Section 18(2)", March 2022 (PDF, copy published by Galway County Council): section 5.7 and Table 2.
- Donegal County Council, Fire Services Act 1981 – 2003 (text of Section 18(2)).
- Irish Statute Book, Fire Services Act 1981, Section 18.
- NSAI, revision of Irish Standard 291.
This guide is provided for information, based on the public documents listed above. It does not replace them or the rules specific to your clients' premises. Other pages: Legal notice · Terms of sale · Privacy · Security · Home